  Datasheet File OCR Text:
  product data sheet 3rt2026-1bb40 contactor, ac-3, 11kw/400v, 1no+1nc, dc 24v, 3-pole, sz s0 screw terminal general technical data: product brand name sirius size of the contactor s0 product extension / auxiliary switch yes protection class ip / on the front ip20 protection against electrical shock finger-safe degree of pollution 3 installation altitude / at a height over sea level / maximum m 2,000 ambient temperature ? during storage c -55 ? +80 ? during operating c -25 ? +60 shock resistance ? at rectangular impulse ? at dc 10g / 5 ms, 7,5g / 10 ms ? at sine pulse ? at dc 15g / 5 ms, 10g / 10 ms impulse voltage resistance / rated value kv 6 insulation voltage / rated value v 690 mechanical operating cycles as operating time ? of the contactor / typical 10,000,000 3rt2026-1bb40 page 1/ 07/27/2012 subject to modifications ? copyright siemens ag 2012 7
? of the contactor with added auxiliary switch block / typical 10,000,000 ? of the contactor with added electronics-compatible auxiliary switch block / typical 5,000,000 main circuit: number of nc contacts / for main contacts 0 number of no contacts / for main contacts 3 operating current ? at ac-1 / at 400 v ? at 40 c ambient temperature / rated value a 40 ? at 60 c ambient temperature / rated value a 35 ? at ac-2 / at 400 v / rated value a 25 ? at ac-3 / at 400 v / rated value a 25 ? at ac-4 / at 400 v / rated value a 15.5 operating current ? with 1 current path / at dc-1 ? at 24 v / rated value a 35 ? at 110 v / rated value a 4.5 ? with 2 current paths in series / at dc-1 ? at 24 v / rated value a 35 ? at 110 v / rated value a 35 ? with 3 current paths in series / at dc-1 ? at 24 v / rated value a 35 ? at 110 v / rated value a 35 ? with 1 current path / at dc-3 / at dc-5 ? at 24 v / rated value a 20 ? at 110 v / rated value a 2.5 ? with 2 current paths in series / at dc-3 / at dc-5 ? at 24 v / rated value a 35 ? at 110 v / rated value a 15 ? with 3 current paths in series / at dc-3 / at dc-5 ? at 24 v / rated value a 35 ? at 110 v / rated value a 35 service power ? at ac-2 / at 400 v / rated value kw 11 ? at ac-3 / at 400 v / rated value kw 11 ? at ac-4 / at 400 v / rated value kw 7.5 active power loss / per conductor / typical w 1.6 off-load operating frequency ? at ac 1/h 5,000 3rt2026-1bb40 page 2/ 07/27/2012 subject to modifications ? copyright siemens ag 2012 7
? at dc 1/h 1,500 frequency of operation / at ac-1 / according to iec 60947-6-2 1/h 1,000 frequency of operation / at ac-2 / according to iec 60947-6-2 1/h 750 frequency of operation / at ac-3 / according to iec 60947-6-2 1/h 750 frequency of operation / at ac-4 / according to iec 60947-6-2 1/h 250 control circuit: type of voltage / of the controlled supply voltage dc control supply voltage / 1 ? for dc / rated value v 24 operating range factor control supply voltage rated value / of the magnet coil ? for dc 0.8 ? 1.1 pull-in power / of the solenoid / for dc w 5.9 holding power / of the solenoid / for dc w 5.9 closing delay ? at dc ms 50 ? 170 opening delay ? at dc ms 15 ? 17.5 arcing time ms 10 ? 10 auxiliary circuit: contact reliability / of the auxiliary contacts 1 faulty switching per 100 million (17 v, 1 ma) number of nc contacts / for auxiliary contacts / instantaneous switching 1 number of no contacts / for auxiliary contacts / instantaneous switching 1 operating current / of the auxiliary contacts ? at ac-12 / maximum a 10 ? at ac-15 ? at 230 v a 10 ? at 400 v a 3 ? at dc-12 ? at 48 v a 6 ? at 60 v a 6 ? at 110 v a 3 ? at 220 v a 1 ? at dc-13 ? at 24 v a 10 ? at 48 v a 2 ? at 60 v a 2 3rt2026-1bb40 page 3/ 07/27/2012 subject to modifications ? copyright siemens ag 2012 7
? at 110 v a 1 ? at 220 v a 0.3 short-circuit: design of the fuse link ? for short-circuit protection of the auxiliary switch / required fuse gl/gg: 10 a ? for short-circuit protection of the main circuit ? with type of assignment 1 / required gl/gg lv hrc 3na, diazed 5sb, neozed 5se: 100 a ? at type of coordination 2 / required gl/gg lv hrc 3na, diazed 5sb, neozed 5se: 35a installation/mounting/dimensions: mounting position +/-180 rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5 on vertical mounting surface type of mounting screw and snap-on mounting onto 35 mm standard mounting rail according to din en 50022 type of fixing/fixation / series installation yes width mm 45 height mm 85 depth mm 107 distance, to be maintained, to the ranks assembly / sidewards mm 0 distance, to be maintained, to earthed part / sidewards mm 6 connections: design of the electrical connection ? for main current circuit screw-type terminals ? for auxiliary and control current circuit screw-type terminals type of the connectable conductor cross-section ? for main contacts ? solid 2x (1 ... 2.5 mm2), 2x (2.5 ... 10 mm2) ? finely stranded ? with conductor end processing 2x (1 ... 2.5 mm2), 2x (2.5 ... 6 mm2), 1x 10 mm2 ? for awg conductors / for main contacts 2x (16 ... 12), 2x (14 ... 8) ? for auxiliary contacts ? solid 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2) ? finely stranded ? with conductor end processing 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2) ? for awg conductors / for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14) certificates/approvals: 3rt2026-1bb40 page 4/ 07/27/2012 subject to modifications ? copyright siemens ag 2012 7
general product approval declaration of conformity test certificates other special test certificate type test certificates/test report shipping approval shipping approval other confirmation ul/csa ratings: yielded mechanical performance (hp) ? for single-phase squirrel cage motors ? at 110/120 v / rated value hp 2 ? at 230 v / rated value hp 3 ? for three-phase squirrel cage motors ? at 200/208 v / rated value hp 5 ? at 220/230 v / rated value hp 7.5 ? at 460/480 v / rated value hp 15 ? at 575/600 v / rated value hp 20 operating current (fla) / for three-phase squirrel cage motors ? at 480 v / rated value a 21 ? at 600 v / rated value a 22 contact rating designation / for auxiliary contacts / according to ul a600 / q600 sicherheitsrelevante kenngr??en: b10 value / with high demand rate ? according to sn 31920 1,000,000 t1 value / for proof test interval or service life ? according to iec 61508 a 20 proportion of dangerous failures ? with low demand rate / according to sn 31920 % 40 ? with high demand rate / according to sn 31920 % 73 failure rate (fit value) / with low demand rate 3rt2026-1bb40 page 5/ 07/27/2012 subject to modifications ? copyright siemens ag 2012 7
? according to sn 31920 fit 100 product function ? mirror contact to iec 60947-4-1 yes ? positively driven operation to iec 60947-5-1 no further information: information- and downloadcenter (catalogs, brochures,?) http://www.siemens.com/industrial-controls/catalogs industry mall (online ordering system) http://www.siemens.com/industrial-controls/mall cax online generator: http://www.siemens.com/cax service&support (manuals, certificates, characteristics, faqs,...) http://support.automation.siemens.com/ww/view/en/3rt2026-1bb40/all image database (product images, 2d dimension drawings, 3d models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3rt2026-1bb40 3rt2026-1bb40 page 6/ 07/27/2012 subject to modifications ? copyright siemens ag 2012 7
last change: jul 26, 2012 3rt2026-1bb40 page 7/ 07/27/2012 subject to modifications ? copyright siemens ag 2012 7


▲Up To Search▲   

 
Price & Availability of 3RT20261BB40

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X